| Burning Performance Difference Between The Firepro of Aluminium-plastic Composite Panel And The Common Aluminium-plastic Composite Panel |
Number |
Test item |
| CLass A |
Class B1 |
Common panel |
| Technical idex |
Test result |
|
| Technical idex |
Test result |
|
Test result |
|
|
1 |
Min rest length after burning(mm) |
¡Ý200 |
535 |
>0 |
430 |
0 |
2 |
Average rest length after burning(mm) |
¡Ý350 |
586 |
¡Ý150 |
487 |
0 |
3 |
Average smoke temperature(¡æ) |
¡Ý125 |
112 |
¡Ü200 |
97 |
620 |
| 4 |
Flame height(mm) |
/ |
/ |
<150 |
15 |
15 |
| 5 |
Smoke density grade |
¡Ý15 |
9 |
¡Ü75 |
37 |
28 |
| 6 |
Heat of combusion,MJ/kg |
¡Ý4.2 |
3.2 |
/ |
/ |
/ |
| 7 |
Heat release of combusion,MJ/m2 |
¡Ý16.8 |
0.9 |
/ |
/ |
/ |
| 8 |
The toxicity smoke,mg/l |
Mouse Keep living during catch the poison and it is weight recovered with 3 days |
25.0
pass |
/ |
/ |
/ |
|
|
|
|
|